WE-T113 measures -40 to 125 degrees C and 0 to 100 %RH, with accuracy +/-0.2 degrees C and +/-2 %RH, selectable +/-3 %RH or +/-5 %RH, and resolution 0.1 degrees C and 1 %RH. Sampling period default is 30 s, reporting cycle default 1 hour.
Output is LoRa on 410.125 to 490.125 MHz, 4G, NB or RS485. RS485 address is 1 to 64, LoRa address and net 1 to 99, channel 0 to 83. Baud rates are 4800, 9600, 19200, 38400, 57600 and 115200 bps, and the Modbus default format is 115200, n, 8, 1.
Holding register 0x0000 is the device ID, default 1, and 0x0014 sets the display unit, 0 Celsius or 1 Fahrenheit. To switch to Fahrenheit send 01 06 00 14 00 01 08 0E; the read request 01 04 00 16 00 01 D0 0E answers 01 04 02 00 41 79 00, read as 65 %RH.